Circuit Breaker Selection

 
Nominal
Watts/Ft.
Startup
Temp.
°F
Maximum Length (in feet) vs. Circuit Breaker Size
120 Volt Heaters   240 Volt Heaters
15A 20A 30A 40A   15A 20A 30A 40A
3 50 325 650
0 230 305 325 460 620 650
-20 205 275 325 410 550 650
5 50 225 270 460 540
0 155 205 270 310 415 540
-20 135 180 270 275 370 540
8 50 145 195 210 295 390 420
0 100 130 195 210 200 265 395 420
-20 90 115 175 210 175 235 350 420
10 50 115 150 180 230 305 360
0 85 110 155 180 165 220 325 360
-20 75 100 145 180 150 195 290 360

Notes:

  1. Circuit breakers are sized per article 427-4 of the N.E.C. The heater lengths shown above represent a current of no more than 80% of the breaker's rated size.

  2. When using 240 volt product at 208, 220 or 277 volts, multiply the lengths shown above by the "length" adjustment factor shown in the Voltage Adjustment Table.

  3. When using 2 or more heater cables of different wattage ratings in parallel on a single circuit breaker, divide 15 amps by the maximum footage shown in the 15A column above to arrive at an "amps per foot" figure for each cable. You can then calculate circuit breaker sizes for these combination loads. These "amps per foot" factors include the N.E.C. sizing factor in Article 427-4.

  4. Article 427-22 of the N.E.C. requires ground-fault equipment protection for each branch circuit supplying electric heating equipment. Exceptions to this requirement can be found in the 1996 N.E.C.

 