Application Data
Nelson's VH Heating Panels are suitable for installation on metallic
tanks and vessels for freeze protection or process temperature maintenance
up to 175°F. Any number of heating panels can be installed on a single
tank and connected in parallel or series to minimize electrical
distribution requirements.
For applications in which the fluid may drop below the level of the
heating panel, a dual thermostat arrangement is recommended. One sensor is
installed on the tank to provide temperature control while the second is
installed on the surface of the highest mounted heating panel acting as a
high temperature cutout switch to protect the heater from abnormal
conditions.
The panels are easily attached with suitable banding materials and must
be mounted below the minimum fluid level on the vessel surface.