Circuit Breaker Selection
For SLT Type Cables
|
Catalog
Number
|
Startup
Temp.
°F |
Maximum
Length (in feet) vs. Circuit Breaker Size |
| 15A |
20A |
30A |
40A |
| SLT-1 |
| 0 |
91 |
122 |
183 |
n/a |
| -20 |
83 |
110 |
166 |
n/a |
| SLT-2 |
| 0 |
183 |
244 |
366 |
488 |
| -20 |
165 |
220 |
330 |
440 |
Notes:
-
Maximum
segment length is the maximum continuous heater run with minimal voltage
drop. For breaker loading, multiple heater segments can be installed
in parallel providing no individual length is longer than the maximum
published segment length. For voltages other than 240 VAC, divide
full breaker amperage rating by amps/foot @ startup temperature to
determine maximum total footage allowed.
-
Circuit
breakers are sized per Article 426-4 of the 1999 National Electrical Code.
-
Article
426-28 of the National Electrical Code requires ground-fault equipment
protection for fixed outdoor electrical deicing equipment.
Electrical connections should be made by a licensed electrician.
|
|