About Us Contents Search

blankbar.jpg (2466 bytes)

 

Home
Up

HLT Approvals
HLT Breaker Selection
HLT Construction
HLT Performance
HLT Power Output
HLT Voltage Adjustment  

American Unity, American Pride, American Strength.


Voltage Adjustment Table

Use of Limitrace products at other than rated voltage require minor adjustments to power output and maximum circuit length ratings.

Adjustment Multipliers for Nominal 240 VAC Heaters
Catalog No. 208 VAC 220 VAC 277 VAC Absolute Max. Length
Power Length Power Length Power Length
HLT23 .74 .93 .84 .96 1.30 1.07 785 ft
HLT25 .76 .93 .85 .96 1.29 1.07 620 ft
HLT28 .78 .93 .86 .96 1.25 1.07 460 ft
HLT210 .80 .93 .88 .96 1.23 1.07 375 ft
HLT212 .81 .93 .88 .96 1.21 1.07 335 ft
HLT215 .83 .93 .89 .96 1.19 1.02 270 ft
HLT218 .85 1.01 .91 1.00 1.18 1.00 245 ft
HLT220 .88 1.00 .93 1.00 1.15 1.00 210 ft
 

Copyright © 2005 Nelson Heat Trace. All rights reserved.
 Legal * Terms, Conditions and Warranty Limitations
If you have any questions, please contact us at support@nelsonheaters.com or E-mail the webmaster