Voltage Adjustment Table
|
|
Use of Limitrace products at other than rated voltage require
minor adjustments to power output and maximum circuit length
ratings.
| Adjustment
Multipliers for Nominal 240 VAC Heaters |
| Catalog No. |
208 VAC |
220 VAC |
277 VAC |
Absolute
Max. Length |
| Power |
Length |
Power |
Length |
Power |
Length |
| HLT23 |
.74 |
.93 |
.84 |
.96 |
1.30 |
1.07 |
785 ft |
| HLT25 |
.76 |
.93 |
.85 |
.96 |
1.29 |
1.07 |
620 ft |
| HLT28 |
.78 |
.93 |
.86 |
.96 |
1.25 |
1.07 |
460 ft |
| HLT210 |
.80 |
.93 |
.88 |
.96 |
1.23 |
1.07 |
375 ft |
| HLT212 |
.81 |
.93 |
.88 |
.96 |
1.21 |
1.07 |
335 ft |
| HLT215 |
.83 |
.93 |
.89 |
.96 |
1.19 |
1.02 |
270 ft |
| HLT218 |
.85 |
1.01 |
.91 |
1.00 |
1.18 |
1.00 |
245 ft |
| HLT220 |
.88 |
1.00 |
.93 |
1.00 |
1.15 |
1.00 |
210 ft |
|
|